Commercial · R290

Caldo Commercial DuoCommercial heat pump for buildings and industry

Hotels, gyms, factories and office buildings need plenty of heat and large volumes of hot water. The Caldo Commercial Duo answers with 50 or 92 kW, water up to 78 °C and up to 2,580 litres of hot water per hour: a commercial heat pump with natural R290 refrigerant and a three-phase supply.

Commercial · industrial
Caldorelli Caldo Commercial Duo commercial heat pump
CALDO COMMERCIAL DUOR290 · COP 3.80–5.02
50 / 92 kWCapacity
R290Refrigerant
−25 °CMin. ambient temp.
78 °CMax. water temp.
Applications

Where it fits

50 or 92 kW solutions for commercial projects, with R290 and hot water up to 78°C.

  • Hotels and holiday accommodation
  • Office and service buildings
  • Industrial sites with high hot water demand
  • Gyms, changing rooms and sports centres

Up to 92 kW heating

The 92 kW model delivers 35.2 to 92 kW of heating at 30/35 °C with a COP of up to 5.02; the 50 kW model delivers 18.4 to 49.25 kW.

Hot water to 78 °C

Domestic hot water and heating water both reach 78 °C, with an output of 1,462 or 2,580 litres per hour and a DHW COP of up to 5.62.

Natural R290 refrigerant

A 4.0 kg R290 charge in the 50 kW model and 8.0 kg in the 92 kW, with a Highly compressor. As R290 is flammable (class A3), qualified technicians are required.

Heating and cooling

Reversible operation supplies chilled water from 7 to 30 °C, with 13.8–34.5 kW or 25–66 kW of cooling and an EER of up to 2.8. It runs at outdoor temperatures from −25 to 43 °C.

Made for your project

Technical data

Technical data are nominal values under standard test conditions. Actual performance may vary. Specifications may change without notice.

Power supply380~415V/3Ph/50-60Hz
Operating range−25~43°C
Hot water20~78°C
Heating water20~78°C
Cooling water7~30°C
IP ratingIPX4

Swipe to explore all specifications.

Model50 kW92 kW
Heating capacity (kW) · 30/35°C18.4~49.2535.2~92
Heating power consumption (kW)4.23~12.987.0~23.8
Heating COP3.8~4.33.86~5.02
DHW capacity (kW) · 15/55°C23.8~6840.0~120
DHW COP4.46~5.624.06~5.5
Heated water output (L/h)14622580
Cooling capacity (kW)13.8~34.525~66
EER2.1~2.652.15~2.8
Max. power consumption (kW)2040
Max. current (A)3264
Circuit breaker (A)4080
Power cable size10mm²22mm²
Pipe diameterG1.5"G2"
Sound pressure dB(A)≤62≤65
Max. water flow (m³/h)8.617.2
Net weight (kg)370745
Unit dimensions (mm)1195×980×19002510×979×1882
RefrigerantR290/4.0kgR290/8.0kg

Full 2026 catalogue (PDF)

How to choose the right model

The series has two models, both on a 380–415 V three-phase supply. The 50 kW model produces 1,462 L/h of hot water, needs a 40 A circuit breaker and weighs 370 kg. The 92 kW model reaches 2,580 L/h, needs an 80 A breaker, weighs 745 kg and measures 2510 × 979 × 1882 mm. Compare these figures with the building's heat demand and peak hot water consumption. Have a qualified installer confirm the final sizing.

See the full buying guide
Caldo Commercial Duo

Frequently asked questions

Straight answers on how heat pumps work, efficiency, installation and choosing a Caldorelli series.

Talk to a specialist

How much hot water does the Caldo Commercial Duo produce?

The 50 kW model produces 1,462 litres of hot water per hour and the 92 kW model 2,580 litres per hour. Under 15/55 °C test conditions, DHW capacity is 23.8–68 kW and 40.0–120 kW respectively, and water can reach 78 °C. Hot water is stored in cylinders sized for the building.

Can an industrial heat pump run radiators?

Yes. The Caldo Commercial Duo supplies heating water from 20 to 78 °C, a temperature suited to radiators in existing buildings. Efficiency rises as water temperature falls, so the design should set the lowest flow temperature that still keeps the building comfortable.

What electrical supply does the Caldo Commercial Duo need?

A 380–415 V, 50–60 Hz three-phase supply. The 50 kW model has a maximum power consumption of 20 kW, a maximum current of 32 A, a 40 A breaker and a 10 mm² cable; the 92 kW model needs 40 kW, 64 A, an 80 A breaker and a 22 mm² cable.

Does the Caldo Commercial Duo work in cold climates?

It operates at outdoor temperatures from −25 to 43 °C and is rated IPX4 for outdoor installation. In cold weather, output and COP vary with air temperature, so the unit should be sized for the site's design outdoor temperature.

Let's choose the right system for your project together.

Request a Free Survey

Contact us

Our experts will get back to you shortly to analyse your needs.

For a faster quote, tell us:

  • Building type and floor area
  • Emitters: underfloor heating, radiators or fan coils
  • Domestic hot water needs
  • Pool volume, if relevant

We use your details only to reply to your request. Privacy Policy